Information about refrigerant R454B
R454B (commercially known as Opteon™ XL41) is an HFO-based refrigerant developed specifically as a replacement for R410A in air conditioning systems and heat pumps. It is a blend of HFC and HFO components (R32 and R1234yf). It is classified as A2L (mildly flammable).
TECHNICAL SPECIFICATIONS
- Status
- Virgin
- GWP
- 466
- ODP
- 0
- SAFETY CLASS
- A2L
- UN-NUMBER
- UN 3161
- PACKAGE SIZES
- 12,5 · 61 · 950 L
- COMPOSITION
- R32 68,9 %; R1234yf 31,1 %
Refrigerant R454B overview
Typical applications of R454B:
- Air source heat pumps and air conditioning systems
- Air-to-water and ground source heat pumps
- Medium-sized water chillers
Additional information
2025–2029: Virgin refrigerants >2500 GWP are banned. Only reclaimed/recycled >2500 GWP allowed (new appliances). Reclaimed refrigerants with GWP <2500 can still be used for servicing and maintenance after 2032.
Differences in refrigerants
| Refrigerant | Status | GWP | ODP | Safety Class | UN Number | Composition |
|---|---|---|---|---|---|---|
| R134a | Reclaimed | 1430 | 0 | A1 | UN 3159 | 100 % R134a (1,1,1,2-tetrafluoroethane) |
| R32 | Reclaimed | 677 | 0 | A2L | UN 3252 | 100 % R32 (difluoromethane) |
| R404A | Reclaimed | 3922 | 0 | A1 | UN 3337 | R134a 4 %; R125 44 %; R143a 52 % |
| R407C | Reclaimed | 1774 | 0 | A1 | UN 3340 | R32 23 %; R125 44 %; R134a 52 % |
| R410A | Reclaimed | 2088 | 0 | A1 | UN 3163 | R32 50 %; R125 50 % |
| R449A | Virgin | 1397 | 0 | A1 | UN 1078 | R32 24.3 %; R125 24.7 %; R134a 25.7 %; R1234yf 25.3 % |
| R448A | Virgin | 1387 | 0 | A1 | UN 3163 | R32 26 %; R125 26 %; R134a 21 %; R1234yf 20 %; R1234ze 7 % |
| R1234yf | Virgin | 4 | 0 | A2L | UN 3161 | 100 % R1234yf (2,3,3,3-tetrafluoropropene) |
| R1234ze | Virgin | 7 | 0 | A2L | UN 3161 | 100 % R1234ze (trans-1,3,3,3-tetrafluoropropene) |
| R452A | Virgin | 2140 | 0 | A1 | UN 1078 | R32 11 %; R125 59 %; R1234yf 30 % |
| R513A | Virgin | 573 | 0 | A1 | UN 3163 | R134a 44 %; R1234yf 56 % |
| R454B | Virgin | 466 | 0 | A2L | UN 3161 | R32 68.9 %; R1234yf 31.1 % |
| R455A | Virgin | 146 | 0 | A2L | UN 3161 | R32 21.5 %; R1234yf 75.5 %; R744 (COâ‚‚) 3 % |
Explore these topics
Dive deeper into refrigerant circular economy, free waste management, and the upcoming F-gas regulation.
Our circular economy model
See how recovered refrigerant is returned to circulation in virgin-like condition, step by step.
Free waste management
Collection, transport, and proper handling at no cost. F-gases returned to circulation as reclaimed refrigerants.
F-gas regulation 2026
What the tightening EU F-gas regulation means for the use and procurement of refrigerants.







How can we help?
Eco Scandic is the first company in the Nordic region focused on refrigerant reclamation, restoring refrigerants to virgin-grade quality through advanced recycling.
Our mission is to provide sustainable circular economy solutions that help customers maximize the value of their resources by extending the lifecycle of refrigeration systems while reducing emissions.
Contact us
Fill in the form and we will contact you shortly.